Overview

HP Modular Power Distribution Units (Zero-U/1U Modular PDUs)

 
HP Modular PDUs have a unique modular architecture designed specifically for data center customers who want to maximize power distribution and space efficiencies in the rack. Modular PDUs consist of two building blocks - the Control Unit (core) and the Extension Bar(s) (sticks). The Control Unit is 1U/0U, and the Extension Bars mount directly to the frame of the rack in multiple locations. Available models range from 16A to 48A current ratings, with output connections ranging from four outlets up to 28 outlets. Single phase and three phase core only units have IEC C-19 outlets on the control unit for BladeSystems as well as larger ProLiant, Integrity and HP9000 servers requiring this type of connection.
 
 
What's New
  • New 40 amp 3 phase Modular PDU is a Core Only form factor that connects to a 50 amp 3 phase circuit using the popular CS8365C connector. The new 3 Phase Modular PDU provides 14.4kVA of power and has 6 C19 outputs for connection to a variety of HP equipment. Optional Extension bars can be added to provide up to 42 C-13 outlet per core unit.

Models
North America, Japan, and South America (Except Argentina and Chile)
100 - 127v 1Ø 2.8 kVA Modular PDU, 24A
252663-D71
200 - 240v 1Ø 3.6 kVA Modular PDU, 16A
252663-B24
4.9 kVA Modular PDU, 24A
252663-D72
8.3 kVA Modular PDU, 40A
252663-B21
8.3 kVA Modular PDU, 40A
252663-D73
8.3 kVA Modular PDU, 40A*
252663-D75
4.9 kVA Modular PDU, 24A*
252663-D74
200 - 240v 3Ø 8.6 kVA Modular PDU, 24A 3Ø*
AF512A
14.4 kVA Modular PDU, 40A 3Ø* AF519A
17.3 kVA Modular PDU, 48A 3Ø*
AF511A
     
International (Including Argentina and Chile)
200 - 240v 1Ø 3.6 kVA Modular PDU, 16A
252663-B24
8.3 kVA Modular PDU, 40A
252663-B21
7.3 kVA Modular PDU, 32A
252663-B31
9.2 kVA Modular PDU, 40A
252663-B32
9.2 kVA Modular PDU, 40A*
252663-B34
7.3 kVA Modular PDU, 32A*
252663-B33
380 - 415v 3Ø 11 kVA Modular PDU, 16A 3Ø*
AF513A
22 kVA Modular PDU, 32A 3Ø*
AF518A
 
* These Modular Distribution Unit Kits are "core only" and do not include any PDU extension bars.

Related Options
HP Two C-13 PDU Extension Bars HP Two C-13 PDU Extension Bars
NOTE: Each extension bar has a C-19 input and 7 C-13 receptacles. The option is ideal for core only models of the modular PDUs
AF500A
HP Two Fixed Cord Extension BarsHP Two Fixed Cord Extension Bars
NOTE: Each extension bar has a C-19 input and 7 C-13 receptacles on 13 inch cords attached to the extension bars. The option is ideal for powering 1U servers and components.
351655-B21
Service and Support Offerings
(HP Care Pack Services)
Hardware Installation
U2871A
Hardware Installation (Electronic)
U2871E

Feature List
  • Single input power distribution units with a unique modular design architecture
  • Up to 28 outlet receptacles
  • Zero-U/1U dense rack form factor
  • Easily accessible outlet receptacles and improved cable management
  • Models range from 2.8kVA to 22kVA

Key Features
  • 2.8 kVA to 9.2kVA1Ø models
    • Unique modular design architecture
    • Small form factor with flexible mounting options
    • Up to 4 PDU extension bars
    • Easy installation
    • Consolidate and maximize cord management
    • Easily accessible outlets
  • 8.6 kVA to 22 kVA 3Ø models
    • Unique modular design architecture
    • Small form factor with flexible mounting options
    • Up to 6 C19 outlet receptacles
    • Easy installation in 1U or Zero U configurations
contents
 Overview      Product Highlights      Service and Support, HP Care Pack, and Warranty Information      Modular PDU Family Information      Technical Specifications line.gif (50 bytes)

Product Highlights

Unique Modular Design Architecture

Modular PDUs have unique modular design architecture. This "Building block" concept consists of two main parts, the Control Unit, and the Extension Bar(s). The modular PDUs ship with one Control Unit and up to 4 Extension Bars. The Control Unit is zero-U or 1U rack mountable. Extension Bars mount directly to the rack-frame or the rack extension unit.

1Ø Modular PDUs

  • Each Control Unit is a single-phase unit that branches out to either 2 or 4 single-phase branch circuits.
  • The PDU extension bars can be plugged into the Control Unit, and can be mounted directly to the rack frame, spanning the entire length of the rack.

3Ø Modular PDUs

  • Each Control Unit is a three-phase input that branches out to 6 single-phase branch circuits.
  • Optional extension bars can be added to provide C13 outlets

NOTE: See model selection matrix below for extension bars which come with each


Up to 6 PDU Extension Bars
  • 8.6 kVA to 22 kVA 3 phase Models
    • Each core only 3 phase unit has six IEC C-19 outputs. These Modular PDUs are ideal for BladeSystems and larger ProLiant, Integrity and HP9000 servers that use C-20 inputs. Up to 6 extension bars can be added to all 3 phase core only units to increase flexibility.
  • 3.6 kVA to 9.2 kVA 200 - 240V Models
    • Modular PDUs offer up to four C-13 extension bars with (7) C13 receptacles. Each extension bar is rated up to 16A (3.6kVA), and has a light on the extension bar indicating the power is on.
  • 2.8 kVA 100-127v Model
    • This Modular PDU offers four Nema 5-15P extension bars with (7) NEMA 5-15P receptacles. Each extension bar is rated up to 16A (1.9kVA (Please see note below), and has a lighted on/off switch on the extension bar.

NOTE: The low voltage extension bars are rated at 1.9kVA, but each C-19 receptacle on the core unit of the 2.8 kVA PDU has a 12A circuit breaker (15A circuit breaker derated to 12A). Therefore the most power an extension bar can draw is 1.4kVA.


Easy Installation Installation is quick and easy. Whether you choose to mount the Modular PDU in zero-U or 1U, all required mounting brackets, accessories, and installation instructions are shipped with the product. The Extension Bars come with easy to use, snap-in brackets, which fit directly into the rack frame of HP 9000, 10000, and 10000 G2 Series racks.

Compatibility Ideal for use with the HP 9000, 10000, and 10000 G2 Series Racks, the Modular PDUs are largely designed for the dense rack environment. These Modular PDUs connect directly to the facility input power.
contents
 Overview      Product Highlights      Service and Support, HP Care Pack, and Warranty Information      Modular PDU Family Information      Technical Specifications line.gif (50 bytes)

Service and Support, HP Care Pack, and Warranty Information

Care Pack Services

Care Pack services provide a range of life cycle support options that let you choose the service levels that meet your business requirements, from basic to mission-critical.

A full range of HP Care Pack hardware and software services are available including:

  • Installation and start up
  • Education courses
  • Extended onsite hardware coverage hours from same business day 13 hours, 5 day to 24 hours, 7 days call window with options including 4-hour response or 6-hour Call To Repair
  • Comprehensive range of software technical support for Microsoft, Linux, ProLiant Essentials and VMWare-based IT solutions helping to deliver high level of application availability. Response times range from 30 mins for critical problems to 2 hours.
  • System Management, Performance Services and Mission Critical Support Solution

NOTE: For more information on HP Care Pack services, contact any of our worldwide sales offices or resellers or visit our worldwide Web site on the internet at: http://www.hp.com/hps/carepack
NOTE: For more complete information on HP Services offerings, customers and resellers, please visit us at: http://www.hp.com/hps
NOTE: Additional information regarding worldwide limited warranty and technical support is available at: http://h18004.www1.hp.com/products/servers/platforms/warranty/index.html


Warranty Upgrade Options HP Modular PDUs are backed by a limited 3-year warranty.
When used in the HP 9000, 10000, and 10000 G2 Series Racks, HP PDUs assume the warranty of the HP Rack in which they're installed. HP Care Pack services bought for the HP Rack also extend towards the HP Modular PDU if it is being used inside the HP rack.
contents
 Overview      Product Highlights      Service and Support, HP Care Pack, and Warranty Information      Modular PDU Family Information      Technical Specifications line.gif (50 bytes)

Modular PDU Family Information

Model Selection Matrix
HP Modular PDUs with Extension Bars
2.8 kVA PDU
3.6 kVA PDU
4.9 kVA PDU
7.3 kVA PDU
9.2 kVA PDU
8.3 kVA PDU 9.2 kVA PDU
Part Number
252663-D71
252663-B24
252663-D72
252663-B31
252663-B21
252663-D73 252663-B32
Input Connection (Single Input)
NEMA L5-30P
Detachable input power cord with an IEC 320-C20 inlet*
NEMA L6-30P
IEC 309-32A
Field Wired Terminal
Non-NEMA Locking CS8265C, 50A IEC-309 63A

* The detachable cord can be used only in applications where the total leakage current is less than 3.5 mA.
Output Connections on Modular PDU core
4 IEC 320 C-19
2 IEC 320 C19
4 IEC 320 C-19
4 IEC 320 C-19
4 IEC 320 C-19
4 IEC 320 C-19 4 IEC 320 C-19
Extension Bars 4 with 7 NEMA 5-15R* 2 with 7 IEC 320 C-13 receptacles 4 with 7 IEC 320 C-13 receptacles 4 with 7 IEC 320 C-13 receptacles 4 with 7 IEC 320 C-13 receptacles 4 with 7 IEC 320 C-13 receptacles 4 with 7 IEC 320 C-13 receptacles
Total Receptacles 28 NEMA 5-15R 14 IEC 320 C-13 28 IEC 320 C-13 28 IEC 320 C-13 28 IEC 320 C-13 28 IEC 320 C-13 28 IEC 320 C-13
* The low volt Extension Bars w/5-15 outlets should be used ONLY with the low volt Control Unit that is shipped with the low volt Modular PDU unit.
Current (max) 24A 16A 24A 32A 40A 40A 40A
AC Voltage Range 100-127V 200-240V 200-240V 200-240V 200-240V 200-240V 200-240V
Frequency (Hertz) 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz
Load Capacity (VA) 2880 (@120V) 3680 (@230V) 4992 (@208V) 7360 (@230V) 9200 (@230V) 8320 (@208V) 9200 (@230V)
Output Circuit Breakers 4x15A 2x10A 4x15A 4x15A 4x15A 4x15A 4x15A
Overload Protection Yes, per load group Yes, per load group Yes, per load group Yes, per load group Yes, per load group Yes, per load group Yes, per load group
Indicator Light on main AC Pilot light on the Control Unit Yes Yes Yes Yes Yes Yes Yes
Plugs and Cables
Control Unit Input: 3.6m attached cable with L5-30P Input: Detachable input power cord (country specific) with a IEC320 C-20 inlet Input: 3.6m attached cable with L6-30P Input: 3.6m attached cable with IEC309-32A, Splashproof Input: Hardwire Input: Attached Input cord, Non-NEMA Locking CS8265C, 50A Input: Attached Input cord, IEC-309 63A, Splashproof
Facility power connection NEMA L5-30R

Can also connect directly to the HP R3000 low voltage UPS

Country specific

Can also connect directly to the HP R3000 High Voltage UPS*

NEMA L6-30R
IEC60309 2 pole, 3 wire, 200- 240VAC, 32A

IEC 332C6S, 332R6S, or equivalent

Hard wired to facility power** Non-NEMA CS8264C or CS8269, 50A or equivalent IEC60309 2 pole, 3 wire, 200- 240VAC, 63A

IEC 363C6S, 363R6S, or equivalent

* For the UPS R3000, North America high volt model an additional cable option kit, PN 340653-001 (IEC320-C-19 to L6-20P), is needed to connect a 16A mPDU to the NA high voltage model of the UPS R3000. This cable is also used to connect the PDU to facility power in North America.
** Hardwiring needs to be done by a certified on-site electrician in accordance with the local electrical installation codes) into the facility input.
Extension Bars Input: 2m attached cord with IEC320-C-20.
Output: Each Bar has 8 NEMA 5-15 outlets
(12A max per outlet, 12A max per Bar).
Input: 2m attached cord with IEC320- C-20.
Output: Each Bar has 7 C-13 outlets
(10A max per outlet, 16A max per Bar).
Input: 2m attached cord with IEC320- C-20.
Output: Each Bar has 7 C-13 outlets
(10A max per outlet, 16A max per Bar).
Input: 2m attached cord with IEC320- C-20.
Output: Each Bar has 7 C-13 outlets
(10A max per outlet, 16A max per Bar).
Input: 2m attached cord with IEC320- C-20.
Output: 4 Bars each with 7 C-13 (10A max per outlet, 16A max per Bar); 1 Bar with 4 C-19 (12A max per outlet,
12A max per Bar).
Input: 2m attached cord with IEC320- C-20.
Output: 4 Bars each with 7 C-13 (10A max per outlet, 16A max per Bar)
Input: 2m attached cord with IEC320- C-20.
Output: 4 Bars each with 7 C-13 (10A max per outlet, 16A max per Bar)
Core Only Modular PDUs
 
4.9 kVA PDU
7.3 kVA PDU
8.3 kVA PDU
9.2 kVA PDU
8.6 kVA PDU
11 kVA PDU
14.4 kVA
17.3kVA PDU
22 kVA PDU
Part Number
252663-D74
252663-B33
252663-D75
252663-B34
AF512A
AF513A
AF519A

AF511A
AF518A
Input Connection (Single Input)
Input: 3.6m attached cable with L6-30P
Input: 3.6m attached cable with IEC309-32A, Splashproof
Input: 3.6m Attached Input cord, Non-NEMA Locking CS8265C, 50A
Input: 3.6m Attached Input cord, IEC-309 63A, Splashproof
Input: 3.6m Attached input cord, NEMA L15-30P
Input: 3.6m Attached Input cord, IEC-309 4 pole, 5 wire, 380-415VAC, 16A, Splashproof
Input: 3.6m Attached input cord, CS8365C plug
Input 3.6m Attached Input cord IEC-309 3 pole, 4 wire 200-240VAC 60A Waterproof
Input: 3.6m Attached Input cord, IEC-309 4 pole, 5 wire, 380-415VAC, 32A, Waterproof
Facility power connection
NEMA L6-30R
IEC60309 2 pole, 3 wire, 200- 240VAC, 32A
IEC 332C6S, 332R6S, or equivalent
Non-NEMA CS8264C or CS8269, 50A or equivalent
IEC60309 2 pole, 3 wire, 200- 240VAC, 63A
IEC 363C6S, 363R6S, or equivalent
208V 3 phase 3 pole 4 wire (Delta) NEMA L15-30R
IEC60309 4 pole, 5 wire, 380-415 VAC, 16A
IEC 516C6S, 516R6S, or equivalent
208V 3 phase 3 pole 4 wire (Delta) CS8364C, CS8369, or equivalent
IEC60309 3 pole, 4 wire, 208VAC 60A
IEC 460C9W, 460R9W, or equivalent
4 pole, 5 wire, 380-415 VAC, 32A
IEC 532C6W, 532R6W, or equivalent
Output Connections on Modular PDU core
4 IEC 320 C-19
4 IEC 320 C-19
4 IEC 320 C-19
4 IEC 320 C-19
6 IEC 320 C-19
6 IEC 320 C-19
6 IEC 320 C-19

6 IEC 320 C-19
6 IEC 320 C-19
Extension Bars
None
None
None
None
None
None
None
None
None
Total Receptacles
4 IEC 320 C-19
4 IEC 320 C-19
4 IEC 320 C-19
4 IEC 320 C-19
6 IEC 320 C-19
6 IEC 320 C-19
6 IEC 320 C-19
6 IEC 320 C-19
6 IEC 320 C-19
Current (max)
24A
32A
40A
40A
41.52A, 13.84A/phase
16A
69A, 23A/phase
83.04A
27.68/phase
32A phase
AC Voltage Range
200-240V
200-240V
200-240V
200-240V
208v 3Ø Delta
380-415v 3Ø Wye
208v 3Ø Delta
208v 3Ø Delta
380-415v 3Ø Wye
Frequency (Hertz)
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
Load Capacity (VA)
4992 (@208V)
7360 (@230V)
8320 (@208V)
9200 (@230V)
8600 (@208V)
11000 (@230v)
14393 (@208V)
17300 (@208V)
22000
(@230V)
Output Circuit Breakers
4x15A
2x10A
4x15A
4x15A
6 X 20A
6 X 16A
6 X 20A
6 X 20A
6 X 16A
Overload Protection
Yes, per load group
Yes, per load group
Yes, per load group
Yes, per load group
Yes, per load group
Yes, per load group
Yes, per load group
Yes, per load group
Yes, per load group
       
HP Power Cables Cable Description
Part Number
IEC C-13


4.5 ft (1.37 m), x15
10A, IEC320 C-14 to IEC 320 C-13 cables for connecting devices to the power distribution unit.
142257-007
4.5 ft (1.37 m), x1
142257-006
1.6 ft (0.5m) x1
142257-B28
8 ft (2.5m) x1
142257-002
6 ft (1.83m) x1 10A, IEC320 C-14 to NEMA -15 cables for connecting devices to the low voltage power distribution unit
AF556A
       
IEC C-19 8 ft (2.5m) x 1

16A, IEC C-19 to IEC C-20 for connecting 16A mPDU to R3000 High voltage UPS, international model
295633-B22
12 ft (3.66m) x1 16A, IEC C-19 to NEMA L6-20 for connecting 16A mPDU directly to a facility outlet or R3000 high voltage UPS in North America/Japan
AF593A
Please refer to the Power Cord Matrix for more information on power cords/cable part numbers, input/output descriptions.
http://www.hp.com/go/powercordmatrix.
Disclaimer: HP makes no recommendations regarding power connector manufactures. The model numbers listed in the above tables are strictly for the purpose of providing examples. Please consult a licensed professional to determine the best connector or receptacle for your specific needs.
contents
 Overview      Product Highlights      Service and Support, HP Care Pack, and Warranty Information      Modular PDU Family Information      Technical Specifications line.gif (50 bytes)

Technical Specifications

All PDUs  
Shipping Weight 20.2 lb (9.16 kg)
Operating Temperature 50° to 122° F (10° to 50° C)
Operating Relative Humidity (%) 10% to 90%
Operating Elevation 0 to 10,000 ft (0 to 3048 m)
Storage Temperature -4° to 140° F (-20° to 60° C)
Storage Relative Humidity (%) 5% to 95%
Storage Elevation 0 to 30,000 ft (0 to 9144 m)
Input Plug Length 142 inches (360.7 cm)
Conformance Standards UL, CUL, CE, NOM, D - 16A and 40A models
UL, CUL, NOM - 24A High and Low voltage models
CE, D - 32A model
1Ø 2.8kVA to 9.2kVA  
Mechanical Dimensions (WxHxD) 17.5 x 1.62 x 5.6 in (44.45 x 4.11 x 14.22 cm)
Unit Weight 18 lb (8.16 kg)
Shipping Dimensions (WxHxD) 21.5 x 12.25 x 13.0 in (54.61 x 31.12 x 33.02 cm)
3Ø 8.6 kVA to 22 kVA  
Mechanical Dimensions (WxHxD) 17.5 x 1.62 x 7.5 in (44.45 x 4.11 x 19.22 cm)
Unit Weight 20 lb (9.07 kg)
Shipping Dimensions (WxHxD) 21.5 x 12.25 x 15.0 in (54.61 x 31.12 x 38.1 cm)
Shipping Weight 22.2 lb (10.07 kg)
Kit Contents  
All Modular PDUs All models ship with:
0U/1U Mounting brackets/hardware for Control Unit
Cord Retention bracket for the Control Unit
Tie wraps
Install Card
Sku Specific Kit Contents  
252663-D71 2.8kVA ship with 1.x Control Unit and 4 x NEMA 5-15P Extension Bars
252663-B34 3.6kVA,16A Modular PDU ship with 1 x Control Unit and 2 x Extension Bars, and country specific power cord, Mounting brackets for Extension Bars
252663-B21 9.2kVA, "field wire" Modular PDU ship with 1 x Control Units, 4 x C-13 Extension Bars, Mounting brackets for Extension Bars
252663-D72, 252663-D73, 252663-B31, 252663-B32 ship with 1 x Control Unit and 4 x C-13 Extension Bars, Mounting brackets for Extension Bars
252663-B33, 252663-B34, 252663-D74, 252663-D75, AF512A, AF513A, AF511A, AF518A, and AF519A ship with 1 x Control Unit

Environment-friendly Products and Approach

End-of-life Management and RecyclingHewlett-Packard offers end-of-life HP product return, trade-in, and recycling programs in many geographic areas. For trade-in information, please go to: http://www.hp.com/go/green. To recycle your product, please go to: http://www.hp.com/go/green or contact your nearest HP sales office. Products returned to HP will be recycled, recovered or disposed of in a responsible manner.

The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each product type for use by treatment facilities. This information (product disassembly instructions) is posted on the Hewlett Packard web site at: http://www.hp.com/go/green. These instructions may be used by recyclers and other WEEE treatment facilities as well as HP OEM customers who integrate and re-sell HP equipment.


© Copyright 2008 Hewlett-Packard Development Company, L.P.
The information contained herein is subject to change without notice.

The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.


   DA-11041 17 - Version 17 - November 17, 2008