| Electrical Input |
Maximum input amps |
10A / 1200 watts Φ |
| |
Nominal Input Frequency
|
60 Hz |
| |
Connections
|
NEMA 5-15P (6 foot, 16 gauge
wire) |
| |
Recommended electrical service |
15A 120V |
| Electrical Output |
Output volt amp capacity (VA)
|
500 VA
|
| |
Output watt capacity (Watts)
|
300 W |
| |
Output nominal voltage |
120V AC |
| |
Output frequency regulation |
LINE MODE: Passes line frequency
of 60Hz +/-10%
BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz |
| |
Output voltage regulation |
BATTERY MODE: PWM sine wave
120V +/-5% |
| |
Voltage Wave Shape
|
Simulated sine wave |
| |
Connections
|
(6) total receptacles: (3) NEMA
5-15R with UPS and surge suppression, and (3) NEMA 5-15R with surge suppression
only. |
| Battery |
Full load run time |
5 minutes (300 watts) |
| |
Half load run time |
17 minutes (150 watts) |
| |
DC system voltage |
12 V DC |
| |
Battery charging |
2-4 hours to 90% |
| |
Typical battery lifespan |
3-6 years, depending on usage |
| |
Battery Type |
Sealed lead-acid, maintenance-free |
| Voltage Regulation |
Voltage regulation description |
Line interactive voltage regulation corrects
brownouts as low as 83V back to 120V nominal values |
| Direct pass through |
Voltages of 106V and greater are passed through
to connected equipment unchanged |
| |
Brownout correction |
Input voltages between 83 and 105 are boosted
by 14% |
| LEDs, Alarms & Switches |
Front panel LEDs |
4 LEDs indicate performance conditions: GREEN
"online" / GREEN "voltage regulation enabled" / RED
"on battery" / YELLOW "battery low/replace" |
| Alarms |
Audible alarm with 15 second delay sounds
to indicate loss of utility power. Alarm can be silenced by pressing front
panel alarm cancel button. Once silenced, alarm will re-sound when approximately
2 minutes runtime remain |
| |
Switches |
Includes 2 front panel switches - one main
on/off power switch and one dual function "alarm cancel" / "self
test" button |
| Surge / Noise Suppression |
AC surge suppression |
1920 joules |
| AC surge suppression response time |
Instantaneous |
| |
Data line suppression
|
Single line TEL/DSL surge suppression with
RJ-style phone connectors (center 2 wires protected, 260V clamping), includes
phone cable |
| |
EMI / RFI AC noise suppression |
Yes |
| Line / Battery Transfer |
Transfer time from line power to battery
mode |
2-4 milliseconds |
| |
Low voltage transfer to battery power |
Switches to battery power as line voltage
decreases to 83 volts or less. Resets to line power mode as line voltage
increases to 87V or higher |
| |
High voltage transfer to battery power |
Switches to battery power as line voltage
increases to 147 volts or higher. Resets to line power mode as line voltage
decreases to 143V or less |
| Communications |
Serial Communication |
Intelligent serial communication to provide
alarms, power monitoring, orderly shutdown and many other features. |
| |
Network monitoring port |
Built-in USB port supports on battery, low
battery, and power restored messaging |
| |
Software and cabling |
USB cabling included. HP Power Manager software
available FREE from http://www.hp.com/products/ups. |
| Environmental and Safety |
Operating Temperature |
50° to 104° F (10° to 40°
C). CAUTION: Long term use at ambient higher than 25° C reduces battery
life. The unit shall be fully functional throughout the range. |
| |
Storage Temperature |
32° to 77° F (0° to 25° C).
The unit shall be fully functional after returning to the operating temperature
range. |
| |
Transit Temperature |
-13° to 131° F (-25° to 55°
C). The unit shall be fully functional after returning to the operating
temperature range. |
| |
Operating Relative Humidity |
The unit shall be fully functional from 20
to 80% relative humidity (non-condensing) across the operating temperature
range. |
| |
Non-Operating Relative Humidity |
The unit shall be able to withstand 5 to
95% relative humidity, 38.7° C maximum wet bulb temperature, with no
cosmetic damage. The unit shall be fully functional after returning to the
operating temperature and humidity range. |
| |
Operating Altitude |
0 to 6,600 feet (0 to 2000 meters) (14.7
to 10.1 psia). |
| |
Non-Operating Altitude |
0 to 49,000 feet (0 to 14,900 meters) (14.7
to 4.4 psia) |
| Physical |
Form Factor |
Tower |
| |
Cooling Method |
Convection |
| |
Battery Access |
Battery access door allows user replacement
of UPS batteries |
| |
Unit Dimensions
(W x H x D) |
5.25 x 8.5 x 7.0 in (13.3 x 21.6 x 17.8 cm) |
| |
Shipping Dimensions
(W x H x D) |
8.5 x 12.5 x 10.0 in (21.6 x 31.8 x 25.4
cm) |
| |
Unit Weight |
14.4 lbs (6.5 kg) |
| |
Shipping Weight |
16 lbs (7.3 kg) |
| Warranty |
Product Warranty |
3 years |