Overview

HP Monitored Power Distribution Unit (PDU)

 
The HP Monitored PDUs allow administrators and facility personnel to monitor current draw directly at the rack and per PDU. HP Monitored PDUs are available in both 1 phase and 3 phase and in single and dual input. Power capacity per PDU ranges from ranging from 4.9 kVA up to 22 kVA to provide flexibility in deployment. Available PDU's include full rack models with 39 receptacles on the single input models or with 78 receptacles on the dual input models. Half rack versions are single input and are available in a popular single phase model with 24 C-13 and 3 C-19 receptacles and a high capacity 3 phase model with 12 C-19 receptacles for use in dense BladeSystem environments. The optional PDU Management Module allows for remote monitoring of the PDUs across the network.
 
Full Rack Vertical PDU Model (Ideal for 36U to 47U racks)
1. 3 x C-19 outlets per input6. Power cords
2.36 x C-13 outlets per input7.Mounting and cord retention brackets
3.Color coded load segments 8.Serial number label
4.Front Panel Display and communications port for PDU Management module9.Model number
5.Color coded circuit breakers  

Half Rack Vertical PDU Models S340, S348 and S332
1.Front Panel Display and communications port for PDU Management module4.Serial Number label
5.Model number
2.12 x Color Coded C-19 outlets for Load Segmentation6.Power cord
3.Color coded circuit breakers7.Mounting and cord retention brackets

Half Rack Vertical PDU Models S124 and S132
1.3 x C19 outlets5.Front Panel Display and communications port for PDU Management module
2.Color Coded C19 and C13 outlets for Load Segmentation
6.Mounting and cord retention brackets
3.24 x C13 outlets7-9.Color coded circuit breakers
4.Power cord  

What's New
  • New S340 Monitored PDU is a half height form factor that connects to a 50 amp 3 phase circuit using the popular CS8365C connector. The new S340 has a single input and 12 C19 outputs for connection to a variety of HP equipment.

Models
HP Monitored Power Distribution Unit: Full Rack Version
HP 17.3 kVA S2324 Monitored PDU- dual input, 3Ø24A (NA/JPN)
AF503A
HP 8.6 kVA S1324 Monitored PDU- single input, 3Ø, 24A (NA/JPN)
AF504A
HP 16.6 kVA S2140 Monitored PDU- dual input, 1Ø, 40A (NA/JPN)
AF505A
HP 8.3 S1140 Monitored PDU- single input, 1Ø, 40A (NA/JPN)
AF506A
HP 22.1 kVA S2316 Monitored PDU- dual input, 3Ø, 16A (INTL)
AF507A
HP 11 kVA S1316 Monitored PDU- single input, 3Ø, 16A (INTL)
AF508A
HP 14.7 kVA S2132 Monitored PDU- dual input, 1Ø, 32A (INTL)
AF509A
HP 7.3 kVA S1132 Monitored PDU- single input, 1Ø, 32A (INTL)
AF510A

HP Monitored Power Distribution Unit: Half Rack Version
HP 4.9 kVA S124 Monitored PDU- single input, 1Ø, 24A (NA/JPN)
AF914A
HP 14.4 kVA S340 Monitored PDU- single input, 3Ø, 40A (NA/JPN)
AF536A
HP 17.3 kVA S348 Monitored PDU- single input, 3Ø, 48A (NA/JPN) AF916A
HP 7.3 kVA S132 Monitored PDU- single input, 1Ø, 32A (INTL) AF915A
HP 22 kVA S332 Monitored PDU- single input, 3Ø, 32A (INTL) AF917A
NOTE: "Ø" = number of electrical phases at input.  
contents
 Overview      Product Features      Service and Support, HP Care Pack, and Warranty Information      Related Options      Technical Specifications line.gif (50 bytes)

Product Features

Target Applications and Markets
  • 24/7 data centers
    • The HP Monitored PDU enables data centers to provide full rack power from one or more power distribution units. Available products include vertical rack mount taking 0U of rack space, as well as single or dual input models for increased power redundancy. Half height PDUs are perfect for BladeSystems and dense environments.
  • Power monitoring
    • The HP Monitored PDU provides local and optional remote load monitoring. Each PDU chassis includes two serial ports-#1 for local set-up and configuration and #2 for attachment of the optional remote monitoring module.
      NOTE: Optional remote monitoring with HP PDU Management Module (PN: AF400A)
  • Power display
    • The local user interface consists of a basic control panel that includes a two-digit 7-segment display, a recessed reset button, a scroll/invert button and 6 segment-dedicated LEDs. Local alarms are annunciated for current and voltage excursions.

Customer Challenges/Requirements
  • Easy access to power multiple servers, storage and other rack mount equipment
  • Need more outlets and more power in each rack
  • Require easy and quick access to all power outlets in the back of the rack
  • Monitor power in each rack and each PDU locally or remotely

Model Features - Full-Rack Vertical PDU
  • Single and dual input models
  • Single and three phase inputs
  • 36 C13s + 3 C19s per input (single input models)
  • 72 C13s + 6 C19s per input (dual input models)
  • Unique color-coded load identification
  • Local power monitoring display and optional remote power reporting with the PDU Management Module

Model Features - Half-Rack Vertical PDU
  • Single input Models
    • 3 phase input with 12 x C-19s
    • Single phase input with 24 x C-13 and 3 x C-19
  • Unique color-coded load identification Local power monitoring display and optional remote power reporting with the PDU Management Module

Mounting
  • All monitored PDUs can be mounted to connect to either under floor or overhead electrical whips
  • The 7U high monitored PDU breaker box may impede the cable management arms of some ProLiant servers. HP recommends either using the rack extension kit or placing IT equipment in the 7U space which does not use cable management arms, UPS, KVM, etc.
    • Models S124 and S132 do not have this restriction.
  • Models S340, S348 and S332 include fixed rail and swing out brackets for mounting behind BladeSystem enclosures

Optional HP PDU Management Module
  • The HP PDU Management Module enables you to monitor power environments through comprehensive control of individual HP PDUs. The module can be configured to send alert traps to HP Systems Insight Manager and other SNMP management programs or used as a standalone monitoring system. This flexibility enables you to monitor up to two PDUs through the network connector or serial connector located on the front of the management module. To facilitate day-to-day maintenance tasks, the embedded management software provides detailed system logs.
  • The HP PDU Management Module provides remote monitoring of a PDU by connecting the PDU directly to the network. Monitoring of the PDU can be achieved from anywhere and at anytime via a standard web browser.

NOTE: For additional information on the PDU Management Module please go to:
http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/
power-distribution/module/index.html

contents
 Overview      Product Features      Service and Support, HP Care Pack, and Warranty Information      Related Options      Technical Specifications line.gif (50 bytes)

Service and Support, HP Care Pack, and Warranty Information

HP Care Pack services provide a range of life cycle support options that let you choose the service levels that meet your business requirements, from basic to mission-critical.

A full range of HP Care Pack hardware and software services are available including:

  • Installation and start up
  • Education courses
  • Extended onsite hardware coverage hours from same business day 13 hours, 5 day to 24 hours, 7 days call window with options including 4-hour response or 6-hour Call To Repair
  • Comprehensive range of software technical support for Microsoft, Linux, ProLiant Essentials and VMware-based IT solutions helping to deliver high level of application availability. Response times range from 30 minutes for critical problems to 2 hours.
  • System Management, Performance Services and Mission Critical Support Solution

NOTE: For more information on HP Care Pack services, contact any of our worldwide sales offices or resellers or visit our worldwide Web site on the internet at: http://www.hp.com/hps/carepack
NOTE: For more complete information on HP Services offerings, customers and resellers, please visit us at:
http://www.hp.com/hps
NOTE: Additional information regarding worldwide limited warranty and technical support is available at:
http://h18004.www1.hp.com/products/servers/platforms/warranty/index.html
NOTE: For additional information on Server Services, Rack and Power Options, please visit: http://h20219.www2.hp.com/services/cache/111072-0-0-225-121.html

NOTE: The information contained herein is subject to change without notice and is provided "as is" without warranty of any kind.
NOTE: The warranties for HP products and services are set forth in the express limited warranty statements accompanying such products and services.
NOTE: Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.

contents
 Overview      Product Features      Service and Support, HP Care Pack, and Warranty Information      Related Options      Technical Specifications line.gif (50 bytes)

Related Options

HP PDU Extension BarsHP C-13 PDU Extension Bar Kit, pair
NOTE: Each extension bar has a C-20 input cord and 7 x C-13 receptacles.
AF500A
HP Fixed Cord Extension Bar Kit, pair
NOTE: Each extension bar has a C-20 input cord and 7 attached 13 inch C-13 power cords for use with 1U servers.
351655-B21
NOTE: Extension bars may be used with any HP Monitored PDU that has C-19 outlets. 

HP PDU Management ModuleHP PDU Management ModuleAF400A

HP Power Cables10A, IEC320 C-14 to IEC 320 C-13 Cables, 4.5ft (1.37m), 15 pack142257-007
10A, IEC320 C-14 to IEC 320 C-13 Cables, 4.5ft (1.37m), single pack 142257-006
10A, IEC320 C-14 to IEC 320 C-13 Cables, 2.3ft (0.7m), single pack 142257-B28
NOTE: For more information on HP power cords please go to: ftp://ftp.compaq.com/pub/products/servers/ProLiantstorage/power-protection/power-cord-option-kits.pdf 

Service and Support Offerings
(HP Care Pack Services)
Hardware Installation (Electronic)U2871E
contents
 Overview      Product Features      Service and Support, HP Care Pack, and Warranty Information      Related Options      Technical Specifications line.gif (50 bytes)

Technical Specifications

Full Rack Vertical PDU Dual Input Models
Model Number
S2324 (NA/JPN)
S2140 (NA/JPN)
S2316 (INTL)
S2132 (INTL)
Part number
AF503A
AF505A
AF507A
AF509A
Input ratings
Voltage (VAC)
~A: 200-240V 60/50Hz 3Ø Delta
~A: 200-240V 60/50Hz 1Ø
~A: 380-415V 50/60Hz 3Ø Wye
~A: 200-240V 50/60Hz 1Ø
~B: 200-240V 60/50Hz 3Ø Delta
~B: 200-240V 60/50Hz 1Ø
~B: 380-415V 50/60Hz 3Ø Wye
~B: 200-240V 50/60Hz 1Ø
Current (Amps)
Branch circuit requirements
208V, 3Ø, 4-wire, 30A
200-240V, 3-wire 50A
380-415V, 3Ø, 5-wire, 16A Category D Breaker
200-240V, 3-wire, 32A Category D Breaker
Input plug/cord rating
NEMA L15-30P x 2
Non-NEMA Locking CS8265C, 50A x 2
IEC60309 516P6 Splashproof
4 pole, 5 wire, 380-415 VAC, 16A x 2
IEC60309 332P6 Splashproof
3 pole, 2 wire, 200- 240VAC, 32A x 2
Input cord length
72in (1.83m)
72in (1.83m)
72in (1.83m)
72in (1.83m)
Facility receptacle needed
NEMA L15-30R x 2
Hubbell CS8264C, CS8269, or equivalent x2
IEC60309 4 pole, 5 wire, 380-415 VAC, 16A
Hubbell C516C6S, C516R6S, or equivalent x2
IEC60309 2 pole, 3 wire, 200- 240VAC, 32A
Hubbell C332C6S, C332R6S, or equivalent x 2
De-rated capacity
24A
40A
n/a
n/a
Output ratings
Voltage (VAC)
~A: 200-240V 60/50Hz 3Ø
~A: 200-240V 60/50Hz 1Ø
~A: 200-240V 50/60Hz 3Ø
~A: 200-240V 50/60Hz 1Ø
~B: 200-240V 60/50Hz 3Ø
~B: 200-240V 60/50Hz 1Ø
~B: 200-240V 50/60Hz 3Ø
~B: 200-240V 50/60Hz 1Ø
Current (Amps)
Outlet rating C-13
10A
10A
10A
10A
C-19
16A
16A
16A
16A
Load segment L3
~A: 13.86A
~A: 20A
~A: 16A
~A: 20A
~B: 13.86A
~B: 20A
~B: 16A
~B: 20A
L2
~A: 13.86A
~A: 20A
~A: 16A
~A: 20A
~B: 13.86A
~B: 20A
~B: 16A
~B: 20A
L1
~A: 13.86A
~A: 20A
~A: 16A
~A: 20A
~B: 13.86A
~B: 20A
~B: 16A
~B: 20A

Maximum Total

~A: 41.6A
~A: 40A
~A: 48A
~A: 32A
~B: 41.6A
~B: 40A
~B: 48A
~B: 32A
Power (Watts)
  Per Line Cord
~A: 8.6 kVA
~A: 8.3 kVA
~A: 11 kVA
~A: 7.3 kVA
~B: 8.6 kVA
~B: 8.3 kVA
~B: 11 kVA
~B: 7.3 kVA
  PDU Total
17.2 kVA
16.6 kVA
22 kVA
14.7 kVA
Number of outlets
Load Segment / Line Cord C-13
~A: 36 (12 per segment)
~A: 36 (12 per segment)
~A: 36 (12 per segment)
~A: 36 (12 per segment)
~B: 36 (12 per segment)
~B: 36 (12 per segment)
~B: 36 (12 per segment)
~B: 36 (12 per segment)
C-19
~A: 3 (1 per segment)
~A: 3 (1 per segment)
~A: 3 (1 per segment)
~A: 3 (1 per segment)
~B: 3 (1 per segment)
~B: 3 (1 per segment)
~B: 3 (1 per segment)
~B: 3 (1 per segment)
PDU total C-13
72
72
72
72
C-19
6
6
6
6
Dimensions & Weights
Product
Product
Product
Product
Product
Product
Height
60 inches (1524 mm)
60 inches (1524 mm)
60 inches (1524 mm)
60 inches (1524 mm)
Width
3.75 inches (95.25 mm)
3.75 inches (95.25 mm)
3.75 inches (95.25 mm)
3.75 inches (95.25 mm)
Depth
2.0 inches (50.8 mm) @ outlets
2.0 inches (50.8 mm)@ outlets
2.0 inches (50.8 mm)@ outlets
2.0 inches (50.8 mm)@ outlets
Weight
27.5 pounds (12.47 Kg)
37.5 pounds (37.5 Kg)
27.5 pounds (12.47 Kg)
27.5 pounds (12.47 Kg)
Shipping
Shipping
Shipping
Shipping
Shipping
Shipping
Height
66.7 inches (1694 mm)
66.7 inches (1694 mm)
66.7 inches (1694 mm)
66.7 inches (1694 mm)
Width
11.0 inches (279.4 mm)
11.0 inches (279.4 mm)
11.0 inches (279.4 mm)
11.0 inches (279.4 mm)
Depth
11.3 inches (287.02 mm)
11.3 inches (287.02 mm)
11.3 inches (287.02 mm)
11.3 inches (287.02 mm)
Weight
42.3 pounds (19.18 Kg)
42.3 pounds (19.18 Kg)
42.3 pounds (19.18 Kg)
42.3 pounds (19.18 Kg)
 
Full Rack Vertical PDU Single Input Models
Model number
S1324 (NA/JPN)
S1140 (NA/JPN)
S1316 (INTL)
S1132 (INTL)
Part number
AF504A
AF506A
AF508A
AF510A
Input ratings
Voltage (VAC)
200-240V 60/50Hz 3Ø Delta
200-240V 60/50Hz
380-415V 50/60Hz 3Ø Wye
200-240V 50/60Hz
Current (Amps)
Branch circuit requirements
208V, 3Φ, 4-wire, 30A
200-240V, 3-wire 50A
380-415V, 3Φ, 5-wire, 16A Category D Breaker
200-240V, 3-wire, 32A Category D Breaker
Input plug/cord rating
NEMA L15-30P
Non-NEMA Locking CS8265C, 50A
IEC60309 516P6 Splashproof
4 pole, 5 wire, 380-415 VAC, 16A
IEC60309 332P6 Slashproof
2 pole, 3 wire, 200 - 240VAC, 32A
Input cord length
72in (1.83m)
72in (1.83m)
72in (1.83m)
72in (1.83m)
Facility receptacle needed
NEMA L15-30R
Hubbell CS8264C or CS8269, 50A or equivalent
IEC60309 4 pole, 5 wire, 380-415 VAC, 16A
Hubbell C516C6S, C516R6S, or equivalent
IEC60309 2 pole, 3 wire, 200- 240VAC, 32A
Hubbell C332C6S or C332R6S, or equivalent
De-rated capacity
24A
40A
n/a
n/a
Output ratings
Voltage (VAC)
200-240V 60/50Hz 1U
200-240V 60/50Hz 1U
200-240V 50/60Hz 1U
200-240V 50/60Hz 1U
Current (Amps)
Outlet rating C-13
10A
10A
10A
10A  
C-19
16A
16A
16A
16A  
Load segment L3
13.86A
20A
16A
20A  
L2
13.86A
20A
16A
20A  
L1
13.86A
20A
16A
20A  
Maximum Total
41.6A
40A
48A
32A  
Power (kVA)
Per line cord
8.6 kVA
8.3 kVA
11 kVA
7.3 kVA
PDU Total
8.6 kVA
8.3 kVA
11 kVA
7.3 kVA
Number of outlets
Load segments C-13
3 load segments
12 x C-13 outlets per segment
1 load segment per electrical phase
3 load segments
12 x C-13 outlets per segment
3 load segments
12 x C-13 outlets per segment
1 load segment per electrical phase
3 load segments
12 x C-13 outlets per segment)
C-19
3 (1 per segment)
3 (1 per segment)
3 (1 per segment)
3 (1 per segment)
PDU total C-13
36
36
36
36
C-19
3
3
3
3
Dimensions & Weights
Product
Height
60 inches (1524 mm)
60 inches (1524 mm)
60 inches (1524 mm)
60 inches (1524 mm)
Width
1.9 inches (48.26 mm)
1.9 inches (48.26 mm)
1.9 inches (48.26 mm)
1.9 inches (48.26 mm)
Depth
2.0 inches (50.8 mm) @ outlets
2.0 inches (50.8 mm)@ outlets
2.0 inches (50.8 mm)@ outlets
2.0 inches (50.8 mm)@ outlets
Weight
25.1 pounds (11.38 Kg)
25.1 pounds (11.38 Kg)
25.1 pounds (11.38 Kg)
25.1 pounds (11.38 Kg)
Shipping
Height
64.8 inches (1645.2 mm)
64.8 inches (1645.2 mm)
64.8 inches (1645.2 mm)
64.8 inches (1645.2 mm)
Width
7.8 inches (198.12 mm)
7.8 inches (198.12 mm)
7.8 inches (198.12 mm)
7.8 inches (198.12 mm)
Depth
9.5 inches (241.3 mm)
9.5 inches (241.3 mm)
9.5 inches (241.3 mm)
9.5 inches (241.3 mm)
Weight
26.1 pounds (11.83 Kg)
26.1 pounds (11.83 Kg)
26.1 pounds (11.83 Kg)
26.1 pounds (11.83 Kg)
 
Half Rack Vertical PDU Models
Model number
S332 (INTL)
S340 (NA/JPN)
S348 (NA/JPN)
Part number
AF917A
AF536A
AF916A
Input ratings
Voltage
(VAC)
380-415V 50/60Hz
3Ø Wye
200-240V 60/50Hz
3Ø Delta
200-240V 60/50Hz
3Ø Delta
Current (Amps)
Branch circuit requirements
380-415V, 3Ø, 5-wire,
32A Category D Breaker
208V, 3Ø, 4-wire, 50A
208V, 3Ø, 4-wire, 60A
Input plug/cord rating
IEC60309 532P7 Watertight
4 pole, 5 wire, 380-415VAC, 32A
Hubbell CS8365C
3 pole, 4 wire
Twist lock
IEC60309 460P9 Watertight
3 Pole, 4 wire, 250VAC, 60A
Input cord length
72 in (1.83m)
96 in (2.43m)
96 in (2.43m)
Facility receptacle needed
IEC309 4 pole, 5 wire, 380-415VAC, 32A
Hubbell HBL532C6W, HBL532R6W, or equivalent
Hubbell CS8364C (connector), CS8369 (receptacle) or equivalent
IEC309 3 Pole, 4 wire, 250VAC, 60A
Hubbell WHBL460C9W, HBL460R9W, or equivalent
De-rated capacity
n/a
 
48A
Output ratings
Voltage (VAC)
200-240V 50/60Hz 1 Ø
200-240V 60/50Hz 1 Ø
200-240V 60/50Hz 1 Ø
Current (Amps)
Outlet rating C-19
16A
16A
16A
Load segment L6
20A
20A
20A
L5
20A
20A
20A
L4
20A
20A
20A
L3
20A
20A
20A
L2
20A
20A
20A
L1
20A
20A
20A
Power (kVA)
22.1 kVA
14.4 kVA
17.3 kVA
Maximum amperage per phase
32 amps / phase
23 amps / phase
27.7 amps / phase
Number of outlets
Load segment /
line cord
C-19
6 load segments
2 outlets per segment
2 load segments per electrical phase
6 load segments
2 outlets per segment
2 load segments per electrical phase
6 load segments
2 outlets per segment
2 load segments per electrical phase)
PDU total
C-19
12
12
12
Dimensions & Weights
Product Height
28.32 inches (719.2 mm)
28.32 inches (719.2 mm)
28.32 inches (719.2 mm)
Width
3.78 inches (96mm)
3.78 inches (96mm)
3.78 inches (96mm)
Depth
3.70 inches (94mm)
3.70 inches (94mm)
3.70 inches (94mm)
Weight
24.2 lbs (11 Kg)
24.2 lbs (11 Kg)
24.2 lbs (11 Kg)
Shipping Height
33.25 inches (844.55 mm)
33.25 inches (844.55 mm)
33.25 inches (844.55 mm)
Width
12.9 inches (327.66 mm)
12.9 inches (327.66 mm)
12.9 inches (327.66 mm)
Depth
10.2 inches (259.08 mm)
10.2 inches (259.08 mm)
10.2 inches (259.08 mm)
Weight
31 lbs (14.1 Kg)
31 lbs (14.1 Kg)
31 lbs (14.1 Kg)
 
Half Rack Vertical PDU Single Input Models
Model number
S124 (NA/JPN)
S132 (INTL)
Part number
AF914A
AF915A
Input ratings
Voltage (VAC)
200-240V 60/50Hz 1U
200-240V 50/60Hz 1U
Current (Amps)
Branch circuit requirements
208V, 1Ø, 3-wire, 30A
200-240V, 1Ø, 3-wire, 32A Category D Breaker
Input Plug/Cord Rating
NEMA L6-30P
IEC60309 332P6 Splashproof
2 pole, 3 wire, 240VAC, 32A
Input cord length
120 in (3.05m)
120 in (3.05m)
Facility receptacle needed
NEMA L6-30R
IEC60309 2 pole, 3 wire, 240VAC, 32A
Hubbell C332C6S, C332R6S, or equivalent
De-rated capacity
24A
n/a
Output ratings
Voltage (VAC)
200-240V 60/50Hz 1U
200-240V 50/60Hz 1U
Current (Amps)
Outlet ratingC-13
10A
10A
C-20
16A
16A
Load segmentL3
20A
20A
L2
20A
20A
L1
20A
20A
Total 
24A
32A
Power (kVA)
4.9 kVA
7.3 kVA
PDU Total
4.9 kVA
7.3 kVA
Number of outlets
Load segments
C-13
3 load segments
8 x C-13 outlets per segment
3 load segments
8 x C-13 outlets per segment
C-19
3 (1 per segment)
3 (1 per segment)
PDU total
C-13
24
24
C-19
3
3
Dimensions & Weights
ProductHeight
28.86 inches (733mm)
28.86 inches (733mm)
Width
3.78 inches (96mm)
3.78 inches (96mm)
Depth
1.97 inches (50mm)
1.97 inches (50mm)
Weight  
ShippingHeight
34.4 inches (874.7 mm)
34.4 inches (874.7 mm)
Width
7.94 inches (201.6mm)
7.94 inches (201.6mm)
Depth
5.13 inches (130.2 mm)
5.13 inches (130.2 mm)
Weight
13.2 pounds (5.99 Kg)
13.1 pounds (5.94 Kg)
 
Disclaimer: HP makes no recommendations regarding power connector manufactures. The manufacturers and model numbers listed in the above tables are strictly for the purpose of providing examples. Please consult a licensed professional to determine the best connector or receptacle for your specific needs.

Environment-friendly Products and Approach

End-of-life Management and RecyclingHewlett-Packard offers end-of-life HP product return, trade-in, and recycling programs in many geographic areas. For trade-in information, please go to: http://www.hp.com/go/green. To recycle your product, please go to: http://www.hp.com/go/green or contact your nearest HP sales office. Products returned to HP will be recycled, recovered or disposed of in a responsible manner.

The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each product type for use by treatment facilities. This information (product disassembly instructions) is posted on the Hewlett Packard web site at: http://www.hp.com/go/green. These instructions may be used by recyclers and other WEEE treatment facilities as well as HP OEM customers who integrate and re-sell HP equipment.


© Copyright 2009 Hewlett-Packard Development Company, L.P.

The information contained herein is subject to change without notice.

The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.

   DA-12118 19 - Version 19 - August 18, 2009