Overview
|
HP Parallel 3 Phase Uninterruptible Power Systems (UPS RP36000/3) | |
| Power protection in the data center is critical to maintain up time, and the increased densities in data centers is driving the need for uninterruptible power with increased power density, power efficiency, and flexibility. The HP RP36000/3 does just that. This pre-racked uninterruptible power systems provides 36 kilowatts (KW) of power or 24KW with N+1 redundancy. Housed in a single rack cabinet, (HP Rack 10000 Series G2 42U) it can be expanded to 60KW with N+1 simply by installing up to 3 additional RP12000/3 UPS Modules. Digital signal processing, UPS paralleling, and a new On-line On Demand hybrid technology answer the demands for density, redundancy, efficiency and flexibility. On-line On Demand combines the efficiency of a line interactive UPS, up to 97%, with the stability of a double conversion on-line UPS when power fluctuates beyond acceptable limits. Hot swappable batteries and electronics modules and an automatic bypass reduce MTTER (mean time to repair) - down time in the event service is needed. | |
![]() |
![]() |
| RP36000/3 Front |
RP36000/3 Rear |
| 1. | Power bus bar | 1. | Power bus bar |
| 2. | Cabling wire tray (6U) |
2. | Input and output connections for RP12000/3 UPS Modules |
| 3. | RP12000/3 UPS Modules (qty3) |
3. | Cabling wire tray (6U) |
| 4. | HP 10000 Series G2 42U rack with front and rear doors | 4. | RP12000/3 UPS Modules (qty3) |
|
| |||
| Models | ||
| HP RP36000/3 | HP RP36000/3 Uninterruptible Power System NA |
AF438A |
| HP RP36000/3 Uninterruptible Power System INTL |
AF439A | |
|
| ||
| Related Options | ||
| Expansion Upgrade for HP RPS36000/3 | HP RP12000/3 UPS Module 6U NA | AF436A |
| HP RP12000/3 UPS Module 6U INTL | AF437A | |
| | ||
| Key Features |
|
|
|
Product Highlights
| NOTE: For a brief, printer friendly data sheet that describes this product and informs you of the essential capabilities and specifications, please visit: http://h71028.www7.hp.com/ERC/downloads/4AA1-5885ENW.pdf. | |
| Superior power conditioning and thermal efficiency with On-line On Demand technology and Unity Rating | When apparent power (VA) equals true power (Watts), the UPS is said to be unity rated (or power factor correction=unity=maximum efficiency). Also, the HP RP36000/3 UPS uses On-line On Demand hybrid technology which operates in line interactive mode during general use to maximize efficiency and minimize heat output. If input voltage fluctuates outside of the established range, such as if a generator comes on line, the UPS switches to double conversion on-line mode to provide the cleanest power possible. This hybrid technology provides 97% efficiency in standard mode, even with out put loads as low as 40% of maximum. |
|
| |
| Superior Battery Management | Each HP RP12000/3 UPS Module incorporates Enhanced Battery Management: an exclusive, patented technology that doubles battery service life, optimizes battery recharge time, and provides advance notice of pending battery failure. With Enhanced Battery Management, you have a lower total cost of ownership and receive the best in the industry protection for your critical equipment. |
| | |
| State-of-the-art UPS Paralleling Technology |
Configured to order, the HP RP36000/3 UPS ships with three HP RP12000/3 UPS Modules, the power bus bar, and the wiring cabinet installed in an HP Rack 10000 G2 Series 42U rack cabinet. Each module houses its own electronics, batteries, and intelligent automatic bypass module for maximum redundancy. A unique patented state-of-the-art UPS paralleling technology allows all the modules to function independently of each other. Should one of the modules fail then the remaining modules seamlessly redistribute the new load requirement through an automatic load sharing process (with transparent transfer time). And since both the logic and electronics are housed in the each of the individual HP RP12000/3 UPS Modules this technology eliminates system-level single point of failure. The base configuration can be configured as either a 36kW UPS or a 24kW parallel UPS with N+1 redundancy. Up to three additional HP RP12000/3 UPS Modules can be added to provide a maximum of 60 kilowatts with N+1 redundancy (in the same rack). With its high speed Digital Signal Processing (DSP) design all necessary information for paralleling is available to all UPS modules and eliminates single points of failure. The load share control algorithms maintain synchronization and load balance by constantly making minute adjustments to variations in the output power requirements. The paralleling technology in the HP RP36000/3 UPS provides the highest level of reliability and system availability. |
| | |
| Ease of serviceability through hot-swappable batteries and electronics modules | The HP RP36000/3 UPS and HP RP12000/3 UPS Modules have a uniquely designed architecture, consisting of separate, hot swappable battery and electronics modules. Further, a built-in intelligent automatic bypass feature ensures continuous power to your connected load even while the modules are being replaced. Ease of maintenance and serviceability
|
| | |
| Increase battery back-up time with up to four Extended Runtime Modules | Each HP RP12000/3 UPS Module supports a maximum of four Extended Runtime Modules (ERM), to further increase your battery back-up time, should you have a sudden brief power outage. Each ERM is 3U high and can be automatically detected and configure when attached to the UPS. The ERMs are pooled so that if the UPS Module they are attached to fails, the ERMs are still available to the remaining UPS Modules in the HP RP36000/3 UPS. For more information on battery back up times, please refer to the Back-up Times Chart. |
| | |
| Remote management increase flexibility | The HP RP36000/3 systems can
be fully configured and monitored from the any of the front management LCDs.
For remote management the HP UPS Management Module is included at no charge
and provides an embedded web interface allowing the UPS to be managed from
anywhere on the network. NOTE: for more information on the UPS Management Module please see: http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/software/module/ups/index.html |
|
| |
| Remote Emergency Power Off Feature | The HP RP36000/3 UPS includes an isolated REPO (Remote Emergency Power Off) port. The REPO feature allows the power to the UPS outlets to be switched off from a remote location. For more information, refer the HP RP36000/3 UPS user manual. |
| | |
| Flexible output configuration | Output may be hardwired to a remote power panel, such as the HP Power Distribution Rack, or optionally via the UPS Output Modules which provide two 3 phase connections per HP RP12000/3 UPS Modules to connect directly to adjacent racks of equipment. |
| | |
| Output Configuration Options | |
| HP Power Distribution Rack | The HP Power Distribution Rack enhances power management in the data center by moving power distribution to the row level. Decentralizing power improves cable management, decreases diagnostic time for problems, and saves installation costs by reducing the size and number of long power feeds required to reach from large wall mounted distribution units. Housed in a single HP Rack 10000 G2 42U rack cabinet, the HP PDR also save floor space and allows you to move heat robbing transformers off of the data center floor improving cooling. Fully redundant inputs and outputs, can power large numbers of racks with shorter cable runs than conventional site level power distribution systems while providing dependable power to protect valuable IT hardware. Individual branch circuit monitoring and redundant management modules insure you can always determine status and power consumption of each attached rack. NOTE: for more information on the HP Power Distribution Rack please see: www.hp.com/go/pdr |
| | |
| Output Modules and Jumpers | Output modules attach directly to each HP RP12000/3 UPS Modules in the configuration. Each output module provides two L15-30R out puts (NA) or 2 IEC 309 516C9 (16A, 3 phase) outlets (INTL). By using 3 phase jumper cables the output modules can be connected directly to HP 3 Phase Modular or Monitored PDUs in several individual racks. Because of the UPS Parallel design even a loss of a HP RP12000/3 UPS Module would not interrupt the load on the output module attached to it. Up to 6 Output Modules can be configured in a fully loaded HP Parallel UPS. |
| | |
| HP UPS Management Module |
The HP UPS Management Module (included) enables you to monitor and manage
power environments through comprehensive control of HP UPSs. The HP UPS
Management Module can support either a single UPS configuration or provides
additional power protection with support for dual redundant UPS configuration
for no-single-point-of-failure. The additional serial ports will provide
greater power management control and flexible monitoring. NOTE: For more information on
the UPS Management Module please see: http://h18004.www1.hp.com/products/servers/proliantstorage/powerprotection/ |
|
|
Service and Support, HP Care Pack, and Warranty Information
| Warranty |
NOTE: The $250,000 Equipment Protection Guarantee is offered only in North America. |
| | |
| HP Care Pack Services | HP Care Pack Services include HP branded hardware options qualified for the server, purchased at the same time or afterwards, internal to the enclosure, as well as 22" and smaller external monitors and rack mounted UPS options. HP Uninterruptible Power Systems will be covered at the same service level and coverage period as the server. For servers or storage systems installed within a rack, service also covers all HP qualified rack options installed within the same rack. NOTE:
For more information on HP Care Pack services, contact any of our worldwide
sales offices or resellers or visit our worldwide Web site on the internet at:
http://www.hp.com/hps/carepack |
|
|
Related Options
| Care Pack Services |
4-Hour On-site Service, 5-Day x 13-Hour Coverage, 3 Years,
Electronic
|
UH804E
|
| 4-Hour On-site Service, 7-Day
x 24-Hour Coverage, 3 Years, Electronic |
UH805E
|
|
| 6-Hour Call to Repair, On-site Service, 7-Day x 24-Hour Coverage, 3 Years, Electronic |
UH806E
|
|
|
|
||
| Power Distribution Rack |
400 Amp Dual Input Power Distribution Rack, NA
|
AF514A
|
| 200 Amp Dual Input Power Distribution Rack, INTL |
AF515A
|
|
| NOTE: For more information on the HP Power Distribution Rack please go to: www.hp.com/go/pdr. | ||
|
|
||
| Extended Runtime Module (WW) |
Extended Runtime Module (WW)
NOTE: HP 3 PHASE UPS supports a maximum of four Extended Runtime Modules (ERM), to further increase your battery back-up time. Each ERM is 3U high and can be automatically detected and configure when attached to the UPS. For more information on battery back up times, please refer to the Back-up Times Chart. |
AF434A
|
|
|
||
| UPS Output Modules |
UPS Output Module, Dual L15-30 (NA)
|
AF440A
|
| UPS Output Module, Dual IEC 516C9 (INTL) |
AF441A
|
|
|
|
||
| 3 Phase Jumper Cables |
L15-30P to L15-30R, 5ft (NA)
|
460151-005
|
| L15-30P to L15-30R, 10ft (NA) |
460151-010
|
|
| L15-30P to L15-30R, 15ft (NA) |
460151-015
|
|
| IEC 516P9 to IEC 516C9, 5ft (INTL) |
460153-005
|
|
| IEC 516P9 to IEC 516C9, 10ft (INTL) |
460153-010
|
|
| IEC 516P9 to IEC 516C9, 15ft (INTL) |
460153-015
|
|
|
|
||
| Rackmount Power Distribution Units (PDUs) and PDU options |
North America/Japan
|
|
| 8.6 kVA Modular PDU, 24A 3Ø |
AF512A
|
|
| HP 8.3 kVA S1324 Monitored PDU- single input, 3Ø, 24A (NA/JPN) |
AF504A
|
|
| HP 17.3 kVA S2324 Monitored PDU- dual input, 3Ø24A (NA/JPN) |
AF503A
|
|
| International | ||
| HP 3phase Modular PDU, 11 kVA, 16A 3Ø |
AF513A
|
|
| HP 11 kVA S1316 Monitored PDU- single input, 3Ø, 16A (INTL) |
AF508A
|
|
| HP 22.1 kVA S2316 Monitored PDU- dual input, 3Ø, 16A (INTL) |
AF507A
|
|
|
|
||
| HP PDU Extension Bars | HP C-13 PDU Extension Bar Kit,
pair NOTE: Each extension bar has a C-20 input cord and 7 x C-13 receptacles. |
AF500A
|
| Fixed Cord Extension Bars, 100
- 240 VAC NOTE: Each extension bar has a C-20 input cord and 7 attached 13 inch C-13 power cords for use with 1U servers. |
351655-B21
|
|
| NOTE: Extension bars may be used with any HP PDU that has C-19 outlets | ||
|
|
||
| HP PDU Management Module | HP PDU Management Module NOTE: For additional information on the PDU Management Module please go to: http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/ power-distribution/module/index.html |
AF400A
|
|
|
||
| HP Power Cords | 10A, IEC320 C-14 to IEC320 C-13 Cables, 4.5ft (1.37m), 15 pack |
142257-007
|
| 10A, IEC320 C-14 to IEC320 C-13 Cables, 4.5ft (1.37m), single 15 pack |
142257-006
|
|
| 10A, IEC320 C-14 to IEC320 C-13 Cables, 1.6ft (0.5m), single pack |
142257-B28
|
|
| 16A, IEC320 C-19 to IEC320 C-20 Cables, 8ft (2.5m), single pack |
295633-B22
|
|
| 16A, IEC320 C-19 to IEC320 C-20 Cables, 6.5ft (2m), single pack |
AF574A
|
|
| 16A, IEC320 C-19 to IEC320 C-20 Cables, 4ft (1.2m), single pack |
AF575A
|
|
| 16A, IEC320 C-19 to IEC320 C-20 Cables, 3ft (1m), single pack |
E7798A
|
|
| NOTE: For more information on HP power cords please go to: ftp://ftp.compaq.com/pub/products/servers/ProLiantstorage/power-protection/power-cord-option-kits.pdf | ||
|
|
||
| Service and Support Offerings
(HP Care Pack Services) |
Hardware Installation (Electronic)
NOTE: Covers installation of additional RP12000/3 UPS modules into an existing RP36000/3. The RP36000/3 must be installed by a qualified electrical contractor. |
U4696E
|
|
|
Technical Specifications
| RP36000/3 Base UPS (NA) | RP12000/3 UPS Expansion Module (NA) | RP36000/3 Base UPS (INTL) | RP12000/3 UPS Expansion Module (INTL) |
| General Characteristics | Power rating (non-redundant) | 36kW/36kVA | 12kW/12kVA | 36kW/36kVA | 12kW/12kVA |
| Power rating (N+1) | 24kW/24kVA | Each unit adds 12kW/12kVA for a maximum of 60kW/60kVA | 24kW/24kVA | Each unit adds 12kW/12kVA for a maximum of 60kW/60kVA | |
| Efficiency |
>97% at 40% load and above
|
>97% at 40% load and above
|
|||
| Heat dissipation | 1113w/3800 BTU | 371w/1266BTU | 1113w/3800 BTU | 371w/1266BTU | |
| Altitude before derating | 1000 meters (3300 ft. ASL) | 1000 meters (3300 ft. ASL) | 1000 meters (3300 ft. ASL) | 1000 meters (3300 ft. ASL) | |
| Output Characteristics | Output connections |
Hardwired to power bus bar or uses optional output modules | Connects to power bus bar or uses optional output modules | Hardwired to power bus bar or uses optional output modules | Connects to power bus bar or uses optional output modules |
| Rated Output voltage |
100-120VAC Phase to Neutral
180-255VAC Phase to Phase 208VAC 3Φ Delta or Wye |
180-240VAC Phase to Neutral
400v 3Φ Wye |
|||
| Output configuration |
50 or 60Hz auto detecting at startup
|
50 or 60Hz auto detecting at startup
|
|||
| Frequency regulation |
0.1Hz free running
|
0.1Hz free running
|
|||
| Load power factor range |
Lagging: 0.7
Leading: 0.9 |
Lagging: 0.7
Leading: 0.9 |
|||
| Total output voltage distortion |
<3% with IT loads (PFC power supplies)
<5% non-linear or non-PFC power supplies |
<3% with IT loads (PFC power supplies)
<5% non-linear or non-PFC power supplies |
|||
| Input Characteristics | Nominal input voltage |
208Y/120V 3 Phase Wye
5 wire 4 pole |
400Y/230V 3 Phase Wye
5 wire 4 pole |
||
| Voltage range |
180 - 255VAC
|
380- 415VAC
|
|||
| Input Amperage |
3 UPS Modules 150 Amps
|
3 UPS Modules 75 Amps
|
|||
|
4 UPS Modules 200 Amps
|
4 UPS Modules 100 Amps
|
||||
|
5 UPS Modules 225 Amps
|
5 UPS Modules 125 Amps
|
||||
|
6 UPS Modules 225Amps
|
6 UPS Modules 160Amps
|
||||
| Battery Characteristics | Battery type |
Valve regulated lead acid, sealed, maintenance free
|
Valve regulated lead acid, sealed, maintenance free
|
||
| Battery runtime (no ERM) |
>5 minutes at 100% load
|
>5 minutes at 100% load
|
|||
| Battery string voltage |
240VDC
|
240VDC
|
|||
| Battery test |
Automatic standard, manual available
|
Automatic standard, manual available
|
|||
| Battery recharge profile |
Enhanced Battery Management 3 stage charging technology
|
Enhanced Battery Management 3 stage charging technology
|
|||
| Battery pre-failure notification |
Yes, up to 30 days advance notification
|
Yes, up to 30 days advance notification
|
|||
| ERM compatibility |
Up to 4 per RP12000/3 UPS Expansion Module.
|
Up to 4 per RP12000/3 UPS Expansion Module.
|
|||
| Physical Characteristics | Dimensions (HxWxD) | 78.7 x 39.7 x 24 in (2000 x 1015 x 597 mm) | 10.3 (6U) x 17.4 x 26 in (267 x 442 x 660 mm) | 78.7 x 39.7 x 24 in (2000 x 1015 x 597 mm) | 10.3 (6U) x 17.4 x 26 in (267 x 442 x 660 mm) |
| Total Chassis Weight without
batteries or electronics |
653 lb. (396 kg.) | 100 lb. (46 kg) | 653 lb. (396 kg.) | 100 lb. (46 kg) | |
| Total Chassis Weight with batteries or electronics | 1274 lb. (578 kg) | 307 lb. (140 kg) | 1274 lb. (578 kg) | 307 lb. (140 kg) | |
| ERM Weight |
170 lb. (77 kg)
|
170 lb. (77 kg)
|
|||
| Communications and Management | Software compatibility |
Ships with HP UPS Management Module
|
Ships with HP UPS Management Module
|
||
| Control Panel |
Two lines by 20 characters
Four menu-driven interface buttons Four status at a glance LEDs 1 per UPS Module |
Two lines by 20 characters
Four menu-driven interface buttons Four status at a glance LEDs 1 per UPS Module |
|||
| Language support |
English, Spanish, French, German
|
English, Spanish, French, German
|
|||
| REPO Port |
Yes, normally open or normally closed available
|
Yes, normally open or normally closed available
|
|||
| Certifications | Safety |
UL1778, CUL
|
CE
|
||
| EMI |
FCC Part 15, Class A
|
EN62040-2, Class A
|
|||
| Surge Protection |
ANSI C62.41, Cat B-3
|
ANSI C62.41, Cat B-3
|
|||
| Hazardous Materials (RoHS) |
EU Directive 2002/95/EC Category 3 (4 of 5)
|
EU Directive 2002/95/EC Category 3 (4 of 5)
|
|||
|
|
|||||
| Estimated Backup Times Chart (Minutes) |
|
Number of modules
|
Total kW Load
|
Internal batteries
|
+ 1 ERM/ Module
|
+ 2 ERM/ Module
|
+ 3 ERM/ Module
|
+ 4 ERM/ Module
|
|
6
|
60
|
9
|
15
|
22
|
29
|
37
|
|
5
|
48
|
6.9
|
17
|
26
|
34
|
44
|
|
4
|
36
|
7.7
|
18
|
28
|
37
|
47
|
|
3
|
24
|
9
|
21
|
32
|
43
|
54
|
| * All configurations are N+1 NOTE: Backup times are estimated for typical applications. Actual performance will depend on load and battery conditions. |
||||||
|
Environment-friendly Products and Approach |
End-of-life Management and Recycling |
Hewlett-Packard offers end-of-life HP product return, trade-in, and recycling programs in many geographic areas. For trade-in information, please go to http://www.hp.com/go/green. To recycle your product, please go to: http://www.hp.com/go/green or contact your nearest HP sales office. Products returned to HP will be recycled, recovered or disposed of in a responsible manner. The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each product type for use by treatment facilities. This information (product disassembly instructions) is posted on the Hewlett Packard web site at: http://www.hp.com/go/green. These instructions may be used by recyclers and other WEEE treatment facilities as well as HP OEM customers who integrate and re-sell HP equipment. |
|
|
||
|
© Copyright 2007 Hewlett-Packard Development Company, L.P. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein. |