Overview
|
HP Data Center Environmental Edge and HP Insight Environmental Observer |
|
|
The new HP Data Center Environmental Edge technology helps you address
one of the most critical issues in today's data centers - power and cooling.
HP Data Center Environmental Edge is an affordable approach to monitoring
your data center environment, resulting in optimal use of data center
capacity and a reduction in energy costs. HP Data Center Environmental
Edge measures, analyzes and visualizes data center environmental parameters,
ensuring complete confidence that you're running a much more efficient
data center.
HP Data Center Environmental Edge bridges the gap between IT and facilities.
HP Data Center Environmental Edge enables both facilities and IT manager's
deeper insight into their current data center environment. |
|
| HP Data Center Environmental Edge Base Stations | |
![]() |
|
| 1. | Air Pressure Base Station |
| 2. | Environmental Base Station |
| 3. | Base Station Gateway |
|
|
Standard Features
| Wireless Network and Network and Network Security | HP Data Center Environmental
Edge sensor and networking devices use 802.15.4 based radios that operate
in the 2.4 GHz industrial and scientific and medical (ISM) unlicensed band.
The HP Data Center Environmental Edge wireless communications low bandwidth
will not interfere with other wireless communications. The HP Data Center
Environmental Edge wireless communications uses a mesh network topology
to transfer information. HP Data Center Environmental Edge wireless systems achieve security at multiple levels: First HP Data Center Environmental Edge wireless communications are not IP-enabled; they therefore are not susceptible to external IP-based passive and active attacks. Second, HP Data Center Environmental Edge network stack uses 128bit-AES cryptograph to provide authentication and data encryption, thereby providing security against rogue admissions and snooping. |
|
|
|
| HP Insight Environmental Observer S/W | HP Insight Environmental Observer S/W key features include: data center environmental visualization; metrics tracking, alarming and historical information, including 1 year of 24x7 Technical Support and Updates. |
|
|
|
| HP Data Center Environmental Edge Environmental Base Station | HP Data Center Environmental Edge Environmental Base Stations are attached to individual racks or CRAH units and collect temperature and humidity data. The HP Data Center Environmental Edge Environmental Base Station is battery powered and reports temperature and humidity information either once every minute or up to once every 5 minutes based on user desired preferences. Environmental Base Stations are simple to mount or attach within the data center environment with a couple of different Mounting Options techniques, and include a one year parts only warranty (excluding batteries). |
|
Server Racks
|
|
|
CRAH/CRAC (Computer Room Air Handlers / Computer Room Air Conditioning)
|
|
|
Other Locations
|
|
|
|
|
| HP Data Center Environmental Edge Rack Sensor Array | HP Data Center Environmental
Edge Rack Sensor Array contains 3 thermistors to measure rack intake and
3 thermistors to measure rack exhaust. NOTE: One year parts only warranty. NOTE: Must be combined with AT516A Environmental Base Station |
|
|
|
| HP Data Center Environmental Edge Plenum Rate Sensor Array | HP Data Center Environmental
Edge Plenum Rated Sensor Array contains 2 plenum rated thermistors and plenum
rated wiring. NOTE: One year parts only warranty. NOTE: Must be combined with AT516A Environmental Base Station |
|
|
|
| HP Data Center Environmental Edge Air Pressure Base Station | HP Data Center Environmental
Edge Air Pressure Base Station assesses the air pressure differential in
raised floor environments. HP recommends one Air Pressure Base Station per
50 m2 / 500 ft2 of data center floor space. NOTE: One year parts only warranty (excluding batteries). |
|
|
|
| HP Data Center Environmental Edge Base Station Gateway | HP Data Center Environmental
Edge Base Station Gateway provides the wireless communication with the HP
Data Center Environmental Edge Base Stations and transmits the data to the
HP Data Center Environmental Edge server. HP recommends at least two Base
Station Gateways per solution. One Base Station Gateway pair supports up
to 200 base stations. Multiple Base Station Gateway pairs can co-exist in
one data center. NOTE: One year parts only warranty (excluding batteries). NOTE: Regional SKU exists |
|
|
|
| Recommended Base Configuration |
NOTE: The installation of the HP Data Center Environmental Edge recommended base configuration does not require any data center downtime to implement.
|
|
|
|
| HP Data Center Environmental Edge Optional Base Stations | |
| HP Data Center Environmental Edge Energy Base Station |
HP Data Center Environmental Edge Energy Base Station
measures kWh (Kilowatt Hours) consumed, Power, Power Factor, Voltage,
Current, THD on each electrical line where installed. Two variants of
the energy meter exist, 208v or 277/480v version with either 200A or 600A
split core CTs. |
|
|
|
| HP Data Center Environmental Edge Water Leak Detection Base Station |
HP Data Center Environmental Edge Water Leak Detection
Base Station detects liquid leakage. NOTE: One year parts only warranty (excluding batteries). |
|
|
|
| HP Data Center Environmental Edge Chilled Water Energy Base Station | HP Data Center Environmental
Edge Chilled Water Energy Base Station measures chilled water flow rate
and temperature of both the supply and return lines NOTE: One year parts only warranty (excluding batteries). |
|
|
Configuration Information
| HP Data Center Environmental Edge Configuration |
|
|
|
Step 1: Determine base quantity needed for the base recommended configuration:
|
|
|
|
Step 2: Determine extra base stations required for increased granularity |
|
|
|
Step 3: Determine optional base stations |
|
|
| HP Data Center Environmental Edge Base SKUs | ||
| Models |
HP Data Center Environmental Edge Server |
AV865A |
| HP Insight Environmental
Observer S/W NOTE: Includes 1 year of 24x7 SW Technical Support and Updates. |
AT515A | |
| HP Data Center Environmental Edge Environmental Base Station | AT516A | |
| HP Data Center Environmental Edge Rack Sensor Array | AT517A | |
| HP Data Center Environmental Edge Air Pressure Base Station | AT518A | |
| HP Data Center Environmental Edge Base Station Gateway | AT519A | |
| HP Data Center Environmental Edge Installer Kit | AT533A | |
|
|
||
| HP Data Center Environmental Edge Optional SKUs | HP Data Center Environmental Edge Plenum Rated Sensor Array | AT526A |
| HP Data Center Environmental Edge Base Station Gateway (EU) | AT519A#B19 | |
| HP Data Center Environmental Edge Base Station Gateway (APJ:UK) | AT519A#ARS | |
| HP Data Center Environmental Edge Base Station Gateway (AUS) | AT519A#ABG | |
| HP Data Center Environmental Edge Base Station Gateway (CN) | AT519A#AKM | |
| HP Data Center Environmental Edge Base Station Gateway (JPN) | AT519A#ABJ | |
| HP Data Center Environmental Edge Base Station Gateway (UK) | AT519A#ACC |
|
|
Support & Service
|
Service and Support Offerings |
NOTE: The HP Care Pack service part numbers below for the HP Data Center Environmental Edge system, cover the server blade and all HP branded hardware options qualified for the server, purchased at the same time or afterwards, internal to the server. | |
| Support Plus | ||
| Support Plus 24, 1 Year | HA110A1 | |
| Support Plus 24, 3 Years | HA110A3 | |
| Installation & Startup | ||
| HP Installation & Startup Service for HP Data Center Environmental Edge | HA114A1 | |
| NOTE: Provides for an integrated hardware and software implementation that includes remote service planning, onsite deployment of hardware and software, installation verification testing and customer orientation. Hardware deployment covers the installation of a single HP Data Center Environmental Edge server, Ethernet network interconnect, and specified sensor options. Software deployment covers the installation and configuration of sensors in the HP Data Center Environmental Edge Software. |
|
|
Technical Specifications
| Wireless RF Specifications | Band | 2.4 GHz, ISM unlicensed band IEEE 802.14.5 MAC |
| Data rate maximum | 250 Kbps | |
| Maximum RF output power | 0dBm +0 dBi omni-directional antenna |
|
| Base Station Gateway Antenna | +2.2dBi | |
| Node to Node Distance | Typical 15m/ 50ft | |
| Regulatory Notices | FCC Part 15, Subpart C, 15.247 U62-SRS100 and U62-THERM |
|
| Industry Canada 7265A-SRS100 and 7265A-THERM |
||
| CE Marking EN 300 328; V1.7.1 (2006-05) and EN 300 440-2 V1.1.2 (2004-07) |
||
|
|
||
| HP Data Center Environmental Edge Environmental Base Station | Housing | ABS plastic L 3.6" x W 2.5" x H 1.2" (L 91.5mm x W 63.5mm x H 30.5mm) |
| Mounting Options | Zip Tie: (4 holes) Accommodates up to 0.18" (4.6mm) width | |
| 3M Command Strips | ||
| Screws: (4 holes) 1.25" x 1.7" (31.75mm x 43.2mm) - - fits up to #6 Machine Screws | ||
| Connectors | HP 14 position I/O connector for use with HP Data Center Environmental Edge Rack Sensor Array | |
| Power Requirements | 4 Approved Batteries (see Approved Batteries Technical Spec) | |
| Typical Life @ 5 min Sample Rate: 5 to 7 years | ||
| Internal Sensed Data: Dew Point | Operating Range: 50ºF-95ºF
(10ºC - 35ºC), 20%RH - 80%RH Accuracy: Nominal +0.86ºF -0.82ºF (+0.48ºC - 0.46ºC) Accuracy over time: After 1 year +0.92ºF - -0.88ºF (0.51ºC - -0.49ºC) After 2 years +0.99ºF - -0.94ºF (.0.55ºC - -0.52ºC) After 3 years +1.06ºF - -0.99ºF (0.59ºC - -0.55ºC) |
|
| Internal Sensed Data: Temperature Sensor | Accuracy: ±0.5ºF (±0.3ºC) Stability: Negligible Operating Range: 32ºF to 122ºF (0ºC to 50ºC) Time Constant: 231sec moving air (typical)C5 |
|
| Environmental | Operating: 32 to 104degF (0 to
40degC) Storage: 14ºF to 140ºF (-10ºC to 60ºC)On-board AC/DC Operating Temperature: 32ºF to 122ºF (0ºC to 50ºC) Storage Temperature: 14ºF to 140ºF (-10ºC to 60ºC) |
|
|
|
||
| HP Data Center Environmental Edge Base Station Gateway | Connectors | RJ45 Ethernet Connection; 2.1x5.5mm 5.0VDC Jack RPSMA Antenna connector |
| Power requirements | Gateway node requires 5.0VDC (±5%)
via supplied power adapter requiring 110-240VAC (50~60Hz) power source (<2W) Supplied with 2 approved batteries (See Approved Battery Technical Spec) for battery backup during 5V power loss. |
|
| Ethernet | RJ45 Ethernet 10Base-T or 100Base-TX
(auto-sensing) Ethernet Network Security:SSL v3, SSH2, Rijndael 256-bit encryption, password protection, IP address filtering, locking features, hardened OS and stack |
|
| Environmental | Operating: 32 to 104ºF (0
to 40ºC) Storage: 14ºF to 140ºF (-10ºC to 60ºC) |
|
|
|
||
| HP Data Center Environmental Edge Rack Sensor Array | Connectors | HP 14 position I/O connector for use with HP Data Center Environmental Edge Rack Sensor Array |
| Mounting Options | Rack Sensor Array: 3M Command strips to front and rear rack doors. If no doors then side of rack | |
| Three Point Sensor Array: 3M Command strips to attach where the customer needs temperature and humidity visualization | ||
| External Temperature Sensors | Rack Sensor Array: 6 external
thermistors Three Point Sensor Array: 3 external thermistors Temperature Range: 32ºF to 122ºF (0ºC to 50ºC) Temperature Accuracy 10 to 43ºC: ±0.5ºF (±0.3ºC) Temperature Accuracy 0 to 10 and 43 to 50ºC: ±1.2ºF (±0.7ºC) Time Constant: 30sec moving air; 60sec static air (typical) Resolution: ±0.02ºF at 77ºF (±0.01ºC at 25ºC) Stability: Typically ± 0.0056ºF (0.0031ºC) over 5 years Thermistors: 10k ohm, Type J Curve Thermistor Time Constant: 60sec static air; 30sec moving air (typical) |
|
|
|
||
| HP Data Center Environmental Edge Plenum Rated Sensor Array | Connectors | HP 14 position I/O connector for use with HP Data Center Environmental Edge Rack Sensor Array |
| Mounting Options | 3M Command strips to front and rear rack doors. If no doors then side of rack | |
| External Temperature Sensors | 2 plenum rated thermistors attached
to plenum rated wire Temperature Range: 32ºF to 122ºF (0ºC to 50ºC) Temperature Accuracy 10 to 43ºC: ±0.5ºF (±0.3ºC) Temperature Accuracy 0 to 10 and 43 to 50ºC: ±1.2ºF (±0.7ºC) Time Constant: 30sec moving air; 60sec static air (typical) Resolution: ±0.02ºF at 77ºF (±0.01ºC at 25ºC) Stability: Typically ± 0.0056ºF (0.0031ºC) over 5 years Thermistors: 10k ohm, Type J Curve Thermistor Time Constant: 60sec static air; 30sec moving air (typical) |
|
|
|
||
| HP Data Center Environmental Edge Air Pressure Base Station | Housing | ABS plastic L 4.5" x W 2.6" x H 1.4" (L 114.3mm x W 66.1mm x H 35.6mm) |
| Mounting Options | Screw: (4 holes) 1.7" x 1.3" (43.2mm x 33.1mm) - fits up to #6 Machine Screws | |
| Zip Tie: (4 holes) Accommodates up to 0.18" width | ||
| 3M Command Strips | ||
| Connectors | 1/8" Barbed Hose Fitting for High and Low Pressure Differential connections | |
| Power Requirements | 4 Approved Batteries (see Approved Batteries Technical Spec) | |
| Typical battery life @ 5 min Sample
Rate: 5 to 7 years Typical battery Life @ 1 min Sample Rate: 4 years |
||
| Sensed Data Pressure Sensor Performance |
Internal 0 to 0.5 in-H2O Air Pressure Differential (room vs. plenum) | |
| Sensed Data High and Low Pressure Ports |
Differential Pressure Range: 0
to 0.5" H2O (0 to 125 Pa) Zero point accuracy: 0.002" H2O (0.5Pa) Span Accuracy: ±3.0% of reading Resolution: ±0.001"H2O (±0.25 Pa) Offset Stability: <0.1 Pa per year |
|
| 0.170 inch inner diameter tubing;
use with up to 6 feet of tubing, cut to length as required during installation (supplied with node; plenum rated UL94V2 tubing). Longer tubing length is allowable, but sensor accuracy and response time may increase; use pressure diffuser tip to prevent foreign contaminates entering sensor (supplied with node) |
||
| Environmental | Operating: 32 to 104ºF (0
to 40ºC) Storage: 14ºF to 140ºF (-10ºC to 60ºC) |
|
|
|
||
| HP Data Center Environmental Edge Universal Base Station | Housing | ABS plastic L 3.6" x W 2.5" x H 1.2" (L 91.5mm x W 63.5mm x H 30.5mm) |
| Mounting Options | Screws: (4 holes) 1.25" x 1.7" (31.75mm x 43.2mm) - fits up to #6 Machine Screws | |
| Power Requirements | Zip Tie: (4 holes) Accommodates up to 0.18" width | |
| 3M Command Strips | ||
| 4 Approved Batteries (see Approved Batteries Technical Spec) | ||
| Analog inputs | Typical Battery Life @ 5 min Sample
Rate: 5 to 7 years Typical Battery Life @ 1 min Sample Rate: 4 years |
|
| 4-20mA: Accuracy: ±1.15% Full Scale Resolution 0.03%v |
||
| 0-10V: Accuracy: ±1.53% Full Scale Resolution 0.03% |
||
|
|
||
| HP Data Center Environmental Edge 200A Current Base Station | Accuracy | ±0.5% (from 1 - 100% FSO) |
| Range | 0 - 200A RMS | |
| Console Display | 2 significant digits for volumetric flow | |
| Environmental | 10°C to 40°C / 20% to 95% RH, non-condensing | |
| Installation | Licensed electrician, circuit downtime not required | |
|
|
||
| HP Data Center Environmental Edge Flow Meter Base Station | Flow Range | 0 to 400fps (based on typical industrial pipe applications this equates to no limitation in terms of volumetric flow) |
| Installation | Non-intrusive ultrasonic flow measurement | |
| Console Display | Volumetric Flow, range adjusted
at installation for min/max Limits |
|
| Resolution | 1/3200th of the installed range | |
| Console Display | 0 significant digits for volumetric flow | |
| Pipe materials | Steel, Copper, Plastic (2-16" diameter) | |
| Accuracy | ±2.8% | |
|
|
||
| HP Data Center Environmental Edge Water Leak Detection Base Station | Leak Detection | Optical sensor detects liquid
contacting surface Adjustable Height |
| Sensor Operating Temperature | -13ºF to 176ºF (-25ºC to 80ºC) | |
|
|
||
| HP Data Center Environmental Edge Installer kit | Kit Contents | Wire Strippers Plenum Rated Zip Ties Command Strips Cable routing clips Thermistor mounting clips |
|
|
||
| Battery Technical Information | Approved Battery | ENERGIZER AA LITHIUM, MODEL# L91, 1.5VDC |
| Battery Life Expectations | Typical Battery Life @ 5 min Sample
Rate: 5 to 7 years Typical Battery Life @ 1 min Sample Rate: 4 years |
|
|
|
||
| HP BCMS | Components | Includes 42 or 84 Split Core
CT's, 60 amp rated each Includes 2 or 4 CT to Ribbon Cable Interface Box Includes 1 data acquisition board |
| Mounting and Installation | Install data acquisition module inside electrical box or in remote electrical box. Voltage connections are routed to data acquisition module. Split Core CT's are connected to Ribbon Cable Interface boxes, which then convert to ribbon cables connected to the data acquisition board. Modbus connection uses Modbus RTU 4wire multi-drop. | |
| Power Requirements | 110-240VAC, 4 wire Data acquisition board can be powered in parallel or separately. |
|
| Sensed Data |
HP EIO software will provide the following data points:
Power per circuit, per phase, and total with warning status |
|
| Accuracy* | Current (amperage): +/-2% Voltage (volts): +/-2% Power (kw): +/-3% |
|
| Installation | Local licensed electrician required for installation and *onsite calibration | |
|
|
||
| HP Energy Meter | Components | Includes HP wireless base station, SquareD ION6200 in single HDM enclosure, and 3 Split Core CT's, both UL and CE rated |
| Mounting and Installation | HDM Dimensions: 11.92"x7.5"x7.88" Wall mount ION6200 enclosure. Voltage and CT connections are routed from source to HDM enclosure. |
|
| Power Requirements | 110-480VAC*,
50/60Hz, up to 2400amps per circuit*,
3 or 4 wire, Wye or Delta. * Depending on model ordered |
|
| Sensed Data |
HP EIO software will provide the following data points:
|
|
| Accuracy* | Current (amperage): +/-1% Voltage (volts): +/-1% Power (kw): +/-2% |
|
| Installation | Local licensed electrician required for installation and *onsite calibration | |
|
|
||
| HP Chilled Water Energy Meter | Components | Includes HP wireless base station, Ultrasonic Flow Meter with remote transducers, and 2 pipe temperature RTD's |
| Mounting and Installation | Ultrasonic transducers are clamped
directly to the chilled water pipe surface. Pipe temperature RTD's are clamped directly to the chilled water pipe surfaces. Control box and wireless node mounted remotely. |
|
| Power Requirements | 110-240VAC, 50/60Hz | |
| Sensed Data |
HP EIO software will provide the following data points:
|
|
| Accuracy | Volumetric Flow: +/-3% Temperature: +/-0.2degC Energy: +/-3% |
|
|
|
||
| Environment-friendly Products and Approach | End-of-life Management and Recycling |
Hewlett-Packard offers end-of-life HP product return, trade-in, and recycling
programs in many geographic areas. For trade-in information, please go
to: http://www.hp.com/go/green.
To recycle your product, please go to: http://www.hp.com/go/green
or contact your nearest HP sales office. Products returned to HP will
be recycled, recovered or disposed of in a responsible manner. |
|
|
||
|
© Copyright 2011 Hewlett-Packard Development Company, L.P. |