R12000/3 |
R8000/3 |
General Characteristics |
| Power Rating |
12KW / 12KVA |
8KW / 8KVA |
| Efficiency |
>97% |
>97% |
| Heat Dissipation |
<371W/1266 BTU/hr. at 100% rated load |
| Cooling |
Fan cooled, temperature microprocessor monitored; front air entry, rear exhaust |
| Audible Noise, Normal Operation |
50 dBA at 1 meter |
| Altitude Before Derating |
1000 meters (3300 ft. ASL) |
1000 meters (3300 ft. ASL) |
Input Characteristics |
| Input Connections |
IEC309 560P9 (NA)
IEC309 532P9 (INTL)
|
NEMA L21-30P (NA)
IEC309 516P9 (INTL)
|
| Input Voltage |
208 Vac and 400 Vac models |
| Voltage Range |
208V model: 180 to 265 Vac (NA)
400V model: 311 to 519 Vac (INTL) |
| Frequency Range |
50 or 60 Hz, ±5 Hz |
| Input Current Distortion |
<5% with IT loads (PFC power supplies) |
| Input Power Factor |
>.99 with IT loads (PFC power supplies) |
| Inrush Current |
Load dependent |
| Input Requirements |
Three-phase, four wire + ground |
| Bypass Source |
Same as input, (single feed) |
| Generator Compatibility |
Fast sync slew rate for generator synchronization |
Output Characteristics |
| Output Connections |
Dual NEMA L15-30 (NA)
Dual IEC309 516P9 (INTL) |
Single NEMA L15-30 (NA)
Single IEC309 516P9 (INTL) |
| Rated Output Voltage |
208V model: 180 to 255 Vac, Ph to Ph
400V model: 180 to 240 Vac, Ph to N |
| Output Configuration |
Three-phase, four wire + ground (3 phase Wye) |
| Output Frequency (nominal) |
50 or 60 Hz auto-detection on startup |
| Frequency Regulation |
0.1 Hz free running |
| Load Power Factor Range |
Lagging: 0.7
Leading: 0.9 |
Total Output
Voltage Distortion |
<3% with IT loads (PFC power supplies)
<5% non-linear or non-PFC power supplies |
Battery Characteristics |
| Battery Type |
Maintenance-free, sealed, valve-regulated lead acid (VRLA) |
| Battery Runtime (Internal) |
13 minutes at 50% load
4.8 minutes at 100% load |
| Battery String Voltage |
240 Vdc |
| Battery Test |
Automatic battery test standard
Manual battery test from front display |
| Battery Recharge Profile |
Enhanced Battery Management three-stage charging technology |
| Battery Cut-off Voltage |
Variable from 1.67 VPC at <5 min. runtime to 1.75 VPC at >90 min. runtime |
| Battery Low Condition |
Announced with alarm |
| Extended Battery Capability |
Yes, add up to four additional 3U battery enclosures (~34 min at 100% load,
>1 hour at 50% load) |
|
Physical Characteristics
|
Dimensions (HxWxD)
UPS
EBM |
10.3 (6U) x 17.4 x 26.0 inches
267 x 442 x 660 mm
5.2 (3U) x 17.2 x 26 inches
132 x 437 x 660 mm |
Total Chassis Weight
without batteries or
electronics
Total Chassis Weight
with batteries or
electronics |
100 lb. (46 kg)
307 lb. (140 kg) |
| Total UPS Weight without Batteries |
135 lb. (61 kg) |
| Total UPS Weight with Batteries |
307 lb. (140 kg) |
| EBM Weight |
170 lb. (77 kg) |
Communications and User Interface |
| Software Compatibility |
UPS ships with HP Power Manager software |
| Control panel LCD |
Two lines by 20 characters
Four menu-driven interface buttons
Four status at a glance LEDs |
| Multi Language |
English standard; 20 other languages available |
| Configuration Changes |
User capable, firmware auto configures |
| REPO Port |
Yes |
Warranty & Serviceability |
| Warranty |
3 years parts, 1 year labor, 1 year onsite |
| Serviceability Features |
Hot-swappable batteries
Hot-swappable electronics module
Automated internal maintenance bypass
Auto-configure firmware
Flash firmware upgradeable |
| CarePacks |
Automatically covered by ProLiant CarePacks in same rack.
Installation CarePacks available |
Certifications |
| Safety |
208V model: UL1778, cUL
400V model: CE |
| EMI |
208V model: FCC Part15 Class A
400V model: EN62040-2 Class A |
| Surge Protection |
ANSI C62.41, Cat B-3 |
| Hazardous materials (RoHS) |
EU Directive 2002/95/EC Category 3 (4 of 5) |