The densest, most power packed UPS available - offering HP customers more watts per U than any other UPS - allowing for more valuable rack space to be utilized by all of your server, storage and networking equipment.


Product information

» Overview & Features
» Key benefits
» Specifications
» Questions & Answers

Specifications

R12000/3
R8000/3
General Characteristics
Power Rating
12KW / 12KVA
8KW / 8KVA
Efficiency
>97%
>97%
Heat Dissipation
<371W/1266 BTU/hr. at 100% rated load
Cooling
Fan cooled, temperature microprocessor monitored; front air entry, rear exhaust
Audible Noise, Normal Operation
50 dBA at 1 meter
Altitude Before Derating
1000 meters (3300 ft. ASL)
1000 meters (3300 ft. ASL)
Input Characteristics
Input Connections
IEC309 560P9 (NA)
IEC309 532P9 (INTL)
NEMA L21-30P (NA)
IEC309 516P9 (INTL)
Input Voltage
208 Vac and 400 Vac models
Voltage Range
208V model: 180 to 265 Vac (NA)
400V model: 311 to 519 Vac (INTL)
Frequency Range
50 or 60 Hz, ±5 Hz
Input Current Distortion
<5% with IT loads (PFC power supplies)
Input Power Factor
>.99 with IT loads (PFC power supplies)
Inrush Current
Load dependent
Input Requirements
Three-phase, four wire + ground
Bypass Source
Same as input, (single feed)
Generator Compatibility
Fast sync slew rate for generator synchronization
Output Characteristics
Output Connections
Dual NEMA L15-30 (NA)
Dual IEC309 516P9 (INTL)
Single NEMA L15-30 (NA)
Single IEC309 516P9 (INTL)
Rated Output Voltage
208V model: 180 to 255 Vac, Ph to Ph
400V model: 180 to 240 Vac, Ph to N
Output Configuration
Three-phase, four wire + ground (3 phase Wye)
Output Frequency (nominal)
50 or 60 Hz auto-detection on startup
Frequency Regulation
0.1 Hz free running
Load Power Factor Range
Lagging: 0.7
Leading: 0.9
Total Output
Voltage Distortion
<3% with IT loads (PFC power supplies)
<5% non-linear or non-PFC power supplies
Battery Characteristics
Battery Type
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Battery Runtime (Internal)
13 minutes at 50% load
4.8 minutes at 100% load
Battery String Voltage
240 Vdc
Battery Test
Automatic battery test standard
Manual battery test from front display
Battery Recharge Profile
Enhanced Battery Management three-stage charging technology
Battery Cut-off Voltage
Variable from 1.67 VPC at <5 min. runtime to 1.75 VPC at >90 min. runtime
Battery Low Condition
Announced with alarm
Extended Battery Capability
Yes, add up to four additional 3U battery enclosures (~34 min at 100% load,
>1 hour at 50% load)
Physical Characteristics
Dimensions (HxWxD)
UPS

EBM
10.3 (6U) x 17.4 x 26.0 inches
267 x 442 x 660 mm
5.2 (3U) x 17.2 x 26 inches
132 x 437 x 660 mm
Total Chassis Weight
without batteries or
electronics

Total Chassis Weight
with batteries or
electronics
100 lb. (46 kg)


307 lb. (140 kg)
Total UPS Weight without Batteries
135 lb. (61 kg)
Total UPS Weight with Batteries
307 lb. (140 kg)
EBM Weight
170 lb. (77 kg)
Communications and User Interface
Software Compatibility
UPS ships with HP Power Manager software
Control panel LCD
Two lines by 20 characters
Four menu-driven interface buttons
Four status at a glance LEDs
Multi Language
English standard; 20 other languages available
Configuration Changes
User capable, firmware auto configures
REPO Port
Yes
Warranty & Serviceability
Warranty
3 years parts, 1 year labor, 1 year onsite
Serviceability Features
Hot-swappable batteries
Hot-swappable electronics module
Automated internal maintenance bypass
Auto-configure firmware
Flash firmware upgradeable
CarePacks
Automatically covered by ProLiant CarePacks in same rack. Installation CarePacks available
Certifications
Safety
208V model: UL1778, cUL
400V model: CE
EMI
208V model: FCC Part15 Class A
400V model: EN62040-2 Class A
Surge Protection
ANSI C62.41, Cat B-3
Hazardous materials (RoHS)
EU Directive 2002/95/EC Category 3 (4 of 5)